Key Features
Product Overview
This filter reactor is applied in high and low voltage filter cabinets. Connected in series with filter capacitors, it is tuned to a specific resonant frequency to absorb harmonic currents of corresponding frequencies in the power grid. Low-voltage power grids contain numerous harmonic sources such as rectifiers, converters and frequency converters. The generated high-order harmonics will seriously endanger the safe operation of the main transformer and other electrical equipment in the system. When the filter reactor is connected in series with capacitors, it can not only effectively absorb grid harmonics, but also improve the power factor of the system, playing a vital role in the safe operation of the power system.
Technical Parameters
Model |
Appropriate capacitor capacity(KVAR) |
Capacitance of the reactor(KVAR) |
Current(A) |
Inductance (mH) |
Size(L*W*H) |
Insulation class |
CKSG-0.610.45-6% |
10 |
0.60 |
12.83 |
3*3.87 |
190*160*170 |
H |
CKSG-0.9/0.4-6% |
15 |
0.90 |
19.24 |
3*2.58 |
190*170*170 |
H |
CKSG-1.2/0.45-6% |
20 |
1.20 |
25.66 |
3*1.94 |
190*170*170 |
H |
CKSG-1.5/0.45-6% |
25 |
1.50 |
32.07 |
3*1.55 |
230*150*190 |
H |
CKSG-1.8/0.45-6% |
30 |
1.80 |
38.49 |
3*1.29 |
230*160*190 |
H |
CKSG-2.4/0.45-6% |
40 |
2.40 |
51.31 |
3*0.97 |
230*170*190 |
H |
CKSG-3.0/0.45-6% |
50 |
3.00 |
64.14 |
3*0.77 |
265*210*230 |
H |
76.97CKSG-3.6/0.45-6% |
60 |
3.60 |
76.97 |
3*0.65 |
265*210*230 |
H |
CKSG-0.7/0.45-7% |
10 |
0.70 |
12.83 |
3*4.52 |
190*160*170 |
H |
CKSG-1.05/0.45-7% |
15 |
1.05 |
19.24 |
3*3.01 |
190*170*170 |
H |
CKSG-1.4/0.45-7% |
20 |
1.40 |
25.66 |
3*2.26 |
230*150*190 |
H |
CKSG-1.75/0.45-7% |
25 |
1.75 |
32.07 |
3*1.81 |
230*160*190 |
H |
CKSG-2.1/0.45-7% |
30 |
2.10 |
38.48 |
3*1.51 |
230*170*190 |
H |
CKSG-2.8/0.45-64.147% |
40 |
2.80 |
51.31 |
3*1.13 |
230*180*190 |
H |
CKSG76.97-3.5/0.45-7% |
50 |
3.50 |
64.14 |
3*0.90 |
265*220*230 |
H |
CKSG-4.2/0.45-7% |
60 |
4.20 |
76.97 |
3*0.75 |
265*220*230 |
H |
CKSG-1.4/0.525-14% |
10 |
1.40 |
11.00 |
3*12.29 |
230*150*190 |
H |
CKSG-2.1/0.525-14% |
15 |
2.10 |
16.49 |
3*8.19 |
230*170*190 |
H |
CKSC-2.8/0.525-14% |
20 |
2.80 |
21.99 |
3*6.15 |
230*180*190 |
H |
CKSG-3.5/0.525-14% |
25 |
3.50 |
27.49 |
3*4.92 |
265*220*230 |
H |
CKSG-4.2/0.525-14% |
30 |
4.20 |
32.99 |
3*4.10 |
265*220*230 |
H |
CK50SG-5.6/0.525-14% |
40 |
5.60 |
43.98 |
3*3.07 |
265*240*230 |
H |
CKSG-7.0/0.525-14% |
50 |
7.00 |
54.98 |
3*2.46 |
290*190*280 |
H |
CKSG-8.4/0.525-14% |
60 |
8.40 |
65.98 |
3*2.05 |
290*210*280 |
H |
Wiring Drawing

Service Conditions
Altitude: not exceeding 1000 m.
Operating temperature: -25°C ~ +45°C, relative humidity not exceeding 90%.
No harmful gases, flammable or explosive materials in surrounding environment.
The surrounding environment shall have good ventilation. If installed inside a cabinet, ventilation equipment shall be additionally equipped.