Key Features
Product Overview
The APF/SVG collects current signals in real time via external CTs and sends them to the signal conditioning circuit, which forwards the processed signals to the controller. The controller decomposes the sampled currents to extract harmonic currents of each order, reactive currents and three-phase unbalanced currents. It compares the collected current components to be compensated with the compensating current already output by the APF/SVG to obtain the deviation value. This value is sent as a real-time compensation signal to the drive circuit, triggering the IGBT converter to inject compensating current into the power grid. Closed-loop control is thereby implemented to realize the compensation function.
Technical Parameters
Category |
Item |
Indicators |
Input |
Operating Voltage |
400V (-20% ~ +20%); 690V (-20% ~ +20%) |
Operating Frequency |
50Hz (-10% ~ +10%) |
|
Current Transformer |
1000:5 ~ 10000:5 |
|
Functions |
Harmonic Compensation |
SVG: 2–13th (50% of rated current) APF: 2–50th |
Harmonic Filtering Rate |
≥90% ≥85% within equipment capacity (Load current distortion rate ≥20%); ≥70% (Load current distortion rate <20%) |
|
Reactive Power Compensation |
-1 ~ +1 adjustable (within equipment capacity) |
|
3-phase Unbalance Compensation |
100% unbalance full compensation (690V model has no 3-phase unbalance compensation function) |
|
Communication Protocol |
Communication Mode |
RS485, Modbus Protocol |
Communication Interface |
RS485 |
|
Upper Computer Software |
Available; all parameters configurable via upper computer |
|
Fault Alarm |
Available; up to 500 fault alarm records |
|
Monitoring |
Independent module monitoring / centralized whole-unit monitoring supported |
|
Technical Index |
Full Response Time |
≤10 ms |
Active Power Loss |
≤2.5% |
|
Cooling Method |
Intelligent Air Cooling |
|
Noise Level |
≤60 dB |
|
Protection Functions |
Overvoltage, undervoltage, overheat, overcurrent, short-circuit and more than 20 types of protection |
|
CT Installation Position |
Load side / Grid side optional |
|
Mechanical Characteristics |
Wall-mounted Cabinet Size |
Same as module dimensions for wall-mount type |
Module Weight |
13kg (35A/30kvar); 24kg (75A/50kvar); 8kg (100A/150A/100kvar); 45kg (200A/150kvar) |
|
Color |
7035 fine texture powder coating |
|
Environmental Requirements |
Operating Temperature |
-10°C ~ +50°C |
Altitude |
<5000 m (Above 1000 m, power derating 1% per additional 100 m) |
|
Relative Humidity |
<95%, non-condensing |
Wiring Drawing


Service Conditions
Ambient temperature: -10°C ~ +50°C
Altitude: ≤5000 m, 1% power derating per 100 m over 1000 m
Relative humidity: <95%, non-condensing
Voltage range: 400V / 690V (-20% ~ +20%)
Frequency: 50Hz (-10% ~ +10%)
Installation: Indoor, free of explosive/corrosive media
Protection: Module IP20+, electronics IP42; IP54 optional