Mahsulotga umumiy nazar
Chiqish reaktori garmoonik kuchlanish va garmoonik tokni filtrlash hamda elektr tarmog'i sifatini yaxshilash uchun chiqish terminaliga o'rnatilishi kerak. Bizning kirish va chiqish reaktorlarimiz yuqori sifatli import qilingan silitsiyli po'lat varaqdan va ilg'or ishlab chiqarish texnologiyasi yordamida ishlab chiqarilgan. Ular zich o'lchamga ega, past issiqlik ko'tarilish va past shovqin darajasiga ega.
Bizning kompaniya tomonidan ishlab chiqarilgan reaktorlar Siemens, ABB, Sanken, Hitachi, Toshiba, Panasonic, Yaskawa, Powtran, Danfoss, Fuji, Eurotherm, LG, OMRON, Hyundai, Schneider, Lenze, Emerson va Convotherm kabi xalqaro va mahalliy brendlarning chastota o'zgartirgichlari bilan mos keladi.
Asosiy xususiyatlar
Elektr ta'minoti boshqa jihozlarga aniq ta'sir (shovqin va ortiqcha kuchlanish) ko'rsatadi
Elektr ta'minotining fazalararo kuchlanish nozikligi nominal kuchlanishning 1,8% dan oshib ketadi
Juday qisqa tutashuvli zanjirlar (kuch transformatorining quvvati VFD ning nominal qiymatidan 10 marta ortiq)
Chiziqdagi tokni kamaytirish uchun bitta zanjirga bir nechta VFD o'rnatilgan
Quvvat omilini to'g'rilash kondensatorlari yoki PFC qurilmalari ishlatilmoqda
Texnik parametrlar
VFD quvvati (kVt) |
Kirish reaktori turi |
Nominal oqim ((A)) |
Umumiy o'lcham L*E*H (mm) |
O'rnatish o'lchami L×E (mm) |
Kuchlanish tushishi (%) |
Индуктивлик (мH) |
Vazn(kg) |
2.2 |
ACL-4.4V/10A |
10 |
155*130*130 |
80/120x60-Φ8 |
2% |
1.401 |
3.5 |
5.5 |
ACL-4.4V/15A |
15 |
155*130*130 |
80/120x60-Φ8 |
2% |
0.934 |
3.6 |
7.5 |
ACL-4.4V/20A |
20 |
155*130*130 |
80/120x60-Φ8 |
2% |
0.701 |
3.6 |
11 |
ACL-4.4V/30A |
30 |
155*130*130 |
80/120x60-Φ8 |
2% |
0.467 |
3.7 |
15 |
ACL-4.4V/40A |
40 |
155*140*130 |
80/120x70-Φ8 |
2% |
0.350 |
5.1 |
18 |
ACL-4.4V/50A |
50 |
155*150*130 |
80/120x80-Φ8 |
2% |
0.280 |
6.0 |
22 |
ACL-4.4V/60A |
60 |
155*150*130 |
80/120x80-Φ8 |
2% |
0.234 |
6.1 |
30 |
ACL-4.4V/80A |
80 |
190*150*160 |
80/150x85-Φ8 |
2% |
0.175 |
9.0 |
37 |
ACL-4.4V/90A |
90 |
190*150*-160 |
80/150x85-Φ8 |
2% |
0.156 |
9.2 |
45 |
ACL-4.4V/120A |
120 |
190*160*160 |
80/150x95-Φ8 |
2% |
0.117 |
10.7 |
55 |
ACL-4.4V/150A |
150 |
230*150*220 |
120/180x85-Φ8 |
2% |
0.093 |
15.6 |
75 |
ACL-4.4V/200A |
200 |
230*150*220 |
120/180x85-Φ8 |
2% |
0.070 |
16.3 |
110 |
ACL-4.4V/250A |
250 |
230*160*220 |
120/180x95-Φ8 |
2% |
0.056 |
19.0 |
132 |
ACL-4.4V/290A |
290 |
265*180*250 |
135/200*90-Φ8 |
2% |
0.048 |
22.0 |
160 |
ACL-4.4V/330A |
330 |
265*190*250 |
135/200*100-Φ8 |
2% |
0.042 |
26.0 |
185 |
ACL-4.4V/390A |
390 |
265*190*250 |
135/200*100-Φ8 |
2% |
0.036 |
27.0 |
220 |
ACL-4.4V/490A |
490 |
290*160*310 |
135/200*100-Φ8 |
2% |
0.029 |
35.1 |
240 |
ACL-4.4V/530A |
530 |
290*160*310 |
135/200*100-Φ8 |
2% |
0.026 |
35.5 |
280 |
ACL-4.4V/600A |
600 |
290*170*310 |
135/200*110-Φ8 |
2% |
0.023 |
39.0 |
300 |
ACL-4.4V/660A |
660 |
290*170*310 |
135/200*110-Φ8 |
2% |
0.021 |
40.0 |
380 |
ACL-4.4V/800A |
800 |
290*190*310 |
135/200*130-Φ8 |
2% |
0.018 |
50.0 |
Ulanish sxemasi

Xizmatlashish shartlari
Balandlik — 1000 metrdan oshmasin.
Ishlash atrof-muhit harorati -25°C dan +45°C gacha,
Namlik 90% dan oshmaydi.
Atrof muhitda zararli gazlar, yonuvchi yoki portlovchi moddalar bo'lmasligi kerak.
Atrof hududda yaxshi ventilyatsiya ta'minlanishi kerak.