BGMJ cylindrical self-healing low-voltage shunt capacitors apply to power factor correction for 50/60Hz low voltage power systems, for local & centralized automatic compensation. It reduces reactive loss and optimizes voltage quality, a nationally recommended energy-saving product. Compliant with GB/T 12747 and IEC 60831-1/2.
Main technical parameters
Rated Voltage: 0.23~1.14kV
Rated Capacity: 1~60kvar
Rated Frequency: 50Hz or 60Hz
Capacitance Tolerance: -3~5%
Active Power Loss: ≤1.2W/kvar
Voltage Withstand Between Poles: 2.15Un for 5 seconds
Maximum Permissible Overvoltage: 1.1Un
Maximum Permissible Overcurrent: 1.3In Self-discharge
Characteristic: The residual voltage shall drop from √2Un to below 50V within 3 minutes after the capacitor is de-energized.
Compliant Standards: GB/T 12747, IEC 60831
Technical Parameters
Type BSMJ |
Rated Voltage (kV) |
Rated Capacity (kvar) |
Rated capaci tance(μF) |
Rated current (Three/Single phase)(A) |
Overall dimension(mm) |
Screw size |
Model |
0.25-5-3YN(1) |
0.25 |
5 |
255 |
6.7/20 |
Φ76*240 |
M12 |
A/B |
0.25-10-3YN(1) |
0.25 |
10 |
510 |
13.3/40 |
Φ86*240 |
M12 |
A/B |
20/0.25-15-3YN(1) |
0.25 |
15 |
764 |
20/60 |
Φ106*240 |
M12 |
A/B |
0.25-20-3YN(1) |
0.25 |
20 |
1019 |
26.7/80 |
Φ116*240 |
M16 |
A/B |
0.25-25-3YN(1) |
0.25 |
25 |
1274 |
33.3/100 |
Φ116*240 |
M16 |
A/B |
0.25-30-3YN(1) |
0.25 |
30 |
1529 |
40/120 |
Φ136*290 |
M16 |
A/B |
0.45-5-3 (1) |
0.45 |
5 |
79 |
6.4/11 |
Φ76*240 |
M12 |
A/B |
0.45-10-3 (1) |
0.45 |
10 |
157 |
12.8/22 |
Φ76*240 |
M12 |
A/B |
0.45-15-3 (1) |
0.45 |
15 |
236 |
19.2/33 |
Φ86*240 |
M12 |
A/B |
0.45-20-3 (1) |
0.45 |
20 |
315 |
25.7/44 |
Φ96*240 |
M16 |
A/B |
0.45-25-3 (1) |
0.45 |
25 |
393 |
32.1/56 |
Φ96*290 |
M16 |
A/B |
0.45-30-3 (1) |
0.45 |
30 |
472 |
38.5/67 |
Φ106*290 |
M16 |
A/B |
0.45-40-3 (1) |
0.45 |
40 |
629 |
51.3/89 |
Φ116*290 |
M16 |
A/B |
Wiring Drawing

Service Conditions
Reclose Locking Protection: After capacitor disconnection, re-energization is permitted only when the residual voltage drops to 10% of the rated voltage. The normal discharge time is approximately 200 seconds. The controller therefore features a reclose locking timer to prevent premature switching.
Rapid Discharge Requirement: When a conventional controller is used, an additional rapid discharge device is required. This requirement does not apply when equipotential switching switches are adopted.
Altitude:Suitable for installation at altitudes of up to 2,000 m.
Ambient Temperature: −25°C ~ +50°C, 24-hour average temperature: ≤ +40°C, Annual average temperature: ≤ +30°C
Ventilation Requirements: Capacitors must operate in a well-ventilated environment. Installation and operation in sealed or poorly ventilated spaces are prohibited.