Proprietates Claves
Product Overview
BGMJ cylindrical self-healing low-voltage shunt capacitors apply to power factor correction for 50/60 Hz low voltage power systems, for local & centralized automatic compensation. It reduces reactive loss and optimizes voltage quality, a nationally recommended energy-saving product. Compliant with GB/T 12747 and IEC 60831-1/2.
Pelagus Technical Parametri
Voltage aestimatum : 0.23–1.14 kV
Capacitas aestimata : 1–60 kvar
Frequentia censita : 50 Hz or 60 Hz
Facultas Tolerantia : −3–5%
Amissa potentiae activae : ≤1.2 W/kvar
Voltage Withstand Between Poles : 2.15 Un for 5 seconds
Maxima Tolerabilis Supratensio : 1.1Un
Maxima Tolerabilis Supracurrentia : 1.3In Self-discharge
Characteristica : Tensio residua cadere debet ab √2Un ad minus quam 50 V intra 3 minuta post dismissionem condensatoris.
Normae Adimpletae : GB/T 12747, IEC 60831
Parametri technici
Typus BSMJ |
Voltage aestimatum (kV) |
Capacitas aestimata (kvar) |
Capacitas Nominalis (μF) |
Currens nominalis (Three/Single phase)(A) |
Dimensio universa (mm) |
Machinae Dimensio |
Modellum |
0.25-5-3YN(1) |
0.25 |
5 |
255 |
6.7/20 |
φ76*240 |
M12 |
A/B |
0.25-10-3YN(1) |
0.25 |
10 |
510 |
13.3/40 |
φ86*240 |
M12 |
A/B |
20/0.25-15-3YN(1) |
0.25 |
15 |
764 |
20/60 |
φ106*240 |
M12 |
A/B |
0.25-20-3YN(1) |
0.25 |
20 |
1019 |
26.7/80 |
φ116*240 |
M16 |
A/B |
0.25-25-3YN(1) |
0.25 |
25 |
1274 |
33.3/100 |
φ116*240 |
M16 |
A/B |
0.25-30-3YN(1) |
0.25 |
30 |
1529 |
40/120 |
φ136*290 |
M16 |
A/B |
0.45-5-3 (1) |
0.45 |
5 |
79 |
6.4/11 |
φ76*240 |
M12 |
A/B |
0.45-10-3 (1) |
0.45 |
10 |
157 |
12.8/22 |
φ76*240 |
M12 |
A/B |
0.45-15-3 (1) |
0.45 |
15 |
236 |
19.2/33 |
φ86*240 |
M12 |
A/B |
0.45-20-3 (1) |
0.45 |
20 |
315 |
25.7/44 |
φ96*240 |
M16 |
A/B |
0.45-25-3 (1) |
0.45 |
25 |
393 |
32.1/56 |
φ96*290 |
M16 |
A/B |
0.45-30-3 (1) |
0.45 |
30 |
472 |
38.5/67 |
φ106*290 |
M16 |
A/B |
0.45-40-3 (1) |
0.45 |
40 |
629 |
51.3/89 |
φ116*290 |
M16 |
A/B |
Dispositio electrica

Status servitii
Reclose Locking Protection: Post capacitor disconnection, re-energization is allowed only when residual voltage falls to 10% of rated voltage. Typical discharge time is approx. 200 seconds. Hence, controller incorporates a reclose locking timer to prevent premature switching.
Requisitum Rapidum Descaricandi: Cum controller conventionalis utitur, dispositivum additivum rapidum descaricandi requiritur. Hoc requisitum non applicatur cum commutatores commutationis equipotentialis adhibentur.
Altitudo: Idoneus pro installatione in altitudinibus usque ad 2 000 m.
Ambiens temperatus; −25°C ~ +50°C, temperatura media per 24 horas: ≤ +40°C, Temperatura media annualis: ≤ +30°C
Requisita Ventilationis: Capacitores in ambiente bene ventilato operari debent. Installatio et operatio in spatiis hermeticis vel pauca ventilatis prohibentur.