MBFK Series Intelligent Electronic Capacitor Switching Controller

Key Features

  • Zero-Crossing Switching: Switches on at voltage zero-crossing and switches off at current zero-crossing, preventing inrush current and overvoltage.
  • Low Power Consumption: Designed for efficient operation with virtually no harmonic generation.
  • Opto-Electrical Isolation: Provides reliable isolation between the control signal and the switching circuit for enhanced safety.
  • Strong EMC Protection: Advanced electromagnetic compatibility (EMC) protection ensures excellent resistance to electrical interference.
  • Controller Compatible: Can be directly connected to dynamic reactive power compensation controllers for efficient capacitor bank switching.
  • Clear Status Indication: LED indicators display switching status, phase loss, switching delay, and power supply conditions.
  • Reliable Performance: Suitable for low-voltage reactive power compensation systems requiring stable and frequent capacitor switching.
Product Description

Product Overview

The MBFK series intelligent electronic capacitor switching switches are available in common compensation and split compensation types. The common compensation type switches three-phase capacitors in a delta connection, while the split compensation type switches single-phase capacitors in a Y connection.

Using single-chip microcomputer technology, the switch controls each capacitor phase according to the phase sequence of the three-phase power supply, enabling smooth switching without inrush current or overvoltage.

With zero surge, low power consumption, long service life, and low failure rate, the MBFK series can replace AC contactors and capacitive non-contact switches and is widely used in low-voltage reactive power compensation systems.

Technical Parameters

Parameter

Specification

Rated Working Voltage

220 VAC ±20% / 380 V

Operating Power Supply

220 V AC

Rated Frequency

50 Hz ±0.5 Hz

Control Voltage

DC 8–18 V

Service Life

≥100,000 switching operations

Switching Capacity

Three-phase: ≤30 kVAr (Delta connection); Single-phase: ≤10 kVAr (Y connection)

Response Time

≤1000 ms

Switching Interval

≥1 second between each switching operation

Continuous Switching Interval

≥30 seconds between two consecutive switching-on operations

Re-energizing Delay

30 seconds after the switch is turned off

Voltage Drop Across Contacts

≤100 mV

On-State Resistance

≤0.003 Ω

Insulation Resistance

≥10 MΩ under normal atmospheric conditions

Dielectric Strength

≥1600 V

Power Consumption

≤1.5 VA

Voltage Distortion

≤5%

Dimensions

160 × 96 × 90 mm

Mounting Dimensions

142 × 80 mm

Wiring Drawing

14.png

Service Conditions

Altitude: not exceeding 2500 m.

Ambient temperature: -25°C ~ +50°C.

Relative humidity: not exceeding 50% at 40°C, and not exceeding 90% at 20°C.

The surrounding environment shall be free of corrosive gases, conductive dust, and flammable & explosive media.

No severe vibration at the installation site.

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000